You have already completed the quiz before. Hence you can not start it again.
Quiz is loading…
You must sign in or sign up to start the quiz.
You must first complete the following:
Results
Quiz complete. Results are being recorded.
Results
Your time:
Time has elapsed
Categories
Not categorized0%
Thank you – your scores have been recorded. You may now close this browser window.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
Current
Review
Answered
Correct
Incorrect
Question 1 of 100
1. Question
Which of the following does a microgrid not do?
Question 2 of 100
2. Question
Which type of microgrid is connected to a traditional utility, capable of operating in island mode, and has multiple generators and sophisticated controls?
Question 3 of 100
3. Question
Microgrids are considered sustainable when their energy sources are renewable.
Question 4 of 100
4. Question
When installing a combined heat and power (CHP) microturbine
Question 5 of 100
5. Question
The components of a typical fuel cell include an anode, cathode, and an electrolyte membrane.
Question 6 of 100
6. Question
Other sources of electrical generation technologies for microgrids include
Question 7 of 100
7. Question
An ESS is commonly referred to in what units?
Question 8 of 100
8. Question
Which of the following is the most common voltage for batteries comprising a small UPS energy storage system?
Question 9 of 100
9. Question
Battery specifications typically include:
Question 10 of 100
10. Question
Batteries are rated according to?
Question 11 of 100
11. Question
Which of the following best describes a 0.5 C-rate (or C/2) during a discharge?
Question 12 of 100
12. Question
Which of the following are alternate types of energy storage?
Question 13 of 100
13. Question
To dispose of batteries properly, contacting the manufacturer is an appropriate first step.
Question 14 of 100
14. Question
In a PV system which is grid connected, which of the following is not necessary for supplying electricity to the utility company?
Question 15 of 100
15. Question
A microinverter typically connects to
Question 16 of 100
16. Question
A battery array is constructed of 144 series modules of 48 parallel LiCoO2 cells (18650s) with a system nominal voltage of 532 Vdc and system nominal capacity 124.8 AH. Calculate the nominal voltage of each cell.
Question 17 of 100
17. Question
An battery array is constructed of 144 series modules of 48 parallel LiCoO2 cells (18650s) with system nominal voltage of 532 Vdc and system nominal capacity of 124.8 AH. Calculate the current delivered at a 2C rate.
Question 18 of 100
18. Question
The ratio of the density of electrolyte to the density of water is specific gravity which correlates to:
Question 19 of 100
19. Question
The battery output conductors are always terminated to the battery before the disconnect.
Question 20 of 100
20. Question
DC disconnect switches, both fusible and non-fusible, share similar traits with ______ across all voltage ranges.
Question 21 of 100
21. Question
Thermal protection in a circuit breaker protects against short circuits and faults, which are drastically larger than overload.
Question 22 of 100
22. Question
What is the final step prior to opening or entering ESS equipment?
Question 23 of 100
23. Question
Single batteries, no longer in strings, do not have to be discharged to a recommended shipping voltage or SOC prior to removal and packing for disposal.
Question 24 of 100
24. Question
An unapproved lubricant used when sliding batteries onto racks could deteriorate the battery enclosures causing them to eventually leak.
Question 25 of 100
25. Question
Acceptance testing procedures for batteries includes:
Question 26 of 100
26. Question
IEE 1187-2013 states that if the manufacturer has not provided sufficient information one should:
Question 27 of 100
27. Question
If you have questions concerning the overall installation of batteries, you should:
Question 28 of 100
28. Question
Li-ion batteries present racking risks because of
Question 29 of 100
29. Question
What is required by OSHA 29 CFR 1910.151(c) if any person is exposed to injurious corrosive materials?
Question 30 of 100
30. Question
Spill containment is dictated by
Question 31 of 100
31. Question
One should never lift or move a battery by its
Question 32 of 100
32. Question
Which of the following are concerns that need to be addressed when staging batteries on a job site?
Question 33 of 100
33. Question
Active ventilation is required for all batteries that may release gas.
Question 34 of 100
34. Question
One should not work from top to bottom when there is a tipping hazard:
Question 35 of 100
35. Question
This image is an example of a:
Question 36 of 100
36. Question
A lithium-ion battery has a 1C rated capacity of 128ah, what is a likely capacity at a 2C-rate?
Question 37 of 100
37. Question
IEEE installation procedures state that as cells are installed one should:
Question 38 of 100
38. Question
It is impossible to lock out voltage from the terminals of batteries other than by providing an insulation barrier.
Question 39 of 100
39. Question
The parallel connection of batteries or battery segments greatly increases the potential of short-circuit current and may change the PPE category and arc-flash boundary.
Question 40 of 100
40. Question
Which of the following are common connectors recommended by battery manufacturers?
Question 41 of 100
41. Question
A common corrosion inhibitor used for battery terminals is:
Question 42 of 100
42. Question
When making battery connections, _____________ could be the result of over-torque.
Question 43 of 100
43. Question
Which finely stranded cable has 19 strands of cable in sizes 18 AWG to 2 AWG, 37 strands of cable in sizes 1 AWG to 4/0 AWG, and 61 strands of cable in sizes 250 kcmil to 500 kcmil?
Question 44 of 100
44. Question
Fine stranded cables are terminated with
Question 45 of 100
45. Question
Voltage drop in dc systems is a __________.
Question 46 of 100
46. Question
The series connections of battery modules require an increase in conductor size.
Question 47 of 100
47. Question
2020 NEC 706.31 Overcurrent Protection states that overcurrent protection devices, either fuses or circuits breakers, used in any dc portion of an ESS shall have the appropriate voltage, current and interrupting ratings for the application.
Question 48 of 100
48. Question
The ampacity of the feeder circuit conductors from the ESS to the wiring system, serving the loads to be serviced by the system, shall not be less than the greater of the:
Question 49 of 100
49. Question
Cable insulation properties and applications are covered in NEC [2017] Table 310.104(A), and/or NEC [2020] Table 310.4(A).
Question 50 of 100
50. Question
The best shield to prevent interference in a BMS is
Question 51 of 100
51. Question
Ethernet cabling must be terminated in a specific pair order
Question 52 of 100
52. Question
What has a practical working limit of 100m?
Question 53 of 100
53. Question
In an ungrounded (floating) PV system, which conductor(s) is (are) switched when disconnected?
Question 54 of 100
54. Question
Grounding is done to limit hazardous ______ exposure.
Question 55 of 100
55. Question
Which of the following can be used to create a bond?
Question 56 of 100
56. Question
Section 250.4(B) Ungrounded Systems, of the NEC covers
Question 57 of 100
57. Question
When a dc system is on the premises, where can the grounding electrode conductor be located?
Question 58 of 100
58. Question
DC systems must be ________
Question 59 of 100
59. Question
Out of the following options, which one is not a part of BMS systems and controls
Question 60 of 100
60. Question
Common types of manufacturers specifications for control and communication wiring include
Question 61 of 100
61. Question
A BMS balances batteries by removing charge from the most-full cells to leave room for charging or adding resistances so the others can catch up.
Question 62 of 100
62. Question
Modbus RTU serial cabling typically requires what at the end of the line?
Question 63 of 100
63. Question
Which of the following governs ESS electrical safety, emergency shutoff, workspace, electrical connections/installation on the customer side of the meter?
Question 64 of 100
64. Question
Safe energy storage equipment, installations, and systems pertain to:
Question 65 of 100
65. Question
NFPA 70, Article 710 states that all ESS equipment shall be listed and labeled or field labeled for its intended use.
Question 66 of 100
66. Question
Energy Management Systems are designed so that they can override any alternate power sources for fire pumps, health care facilities, emergency systems, legally required standby systems and critical operations power systems.
Question 67 of 100
67. Question
Cables used in ESS systems installed in buildings must comply with NEC classifications
Question 68 of 100
68. Question
Li-ion batteries may create thermal injury hazards caused by overheating.
Question 69 of 100
69. Question
What are the causes for internal short circuiting in Lithium-ion battery?
Question 70 of 100
70. Question
The general inspection of batteries and the location of installation should address:
Question 71 of 100
71. Question
Which of the following is an electrical hazard associated with battery energy storage systems?
Question 72 of 100
72. Question
Which of the following batteries requires rewatering?
Question 73 of 100
73. Question
Applying charge to an over-discharged Li-ion battery can result in overheating and fire.
Question 74 of 100
74. Question
Thermal runaway is a common concern for
Question 75 of 100
75. Question
The safety diamond represents:
Question 76 of 100
76. Question
It is safe to charge a lithium battery without a high voltage cutoff.
Question 77 of 100
77. Question
Splash proof goggles are required when working with electrolyte while wearing a face shield
Question 78 of 100
78. Question
Which of the following PPE should be used when placing wet cell batteries in racks?
Question 79 of 100
79. Question
Rain gear can be used to protect from chemical spills without being evaluated per ASTM1296
Question 80 of 100
80. Question
Vaporized lead exposure is a chemical hazard when working in a battery room.
Question 81 of 100
81. Question
Which of the following is not listed as Category 1 PPE for arc flash and shock risk?
Question 82 of 100
82. Question
NFPA 70E Table 130.7(C)15(b) “Arc-Flash PPE Categories for Direct Current (dc) Systems” cannot be used for systems with voltages greater than:
The determination of short circuit current is necessary in order to use Table 130.7(C)(15)(b) of NFPA 70E. The arcing current is calculated at ___% of the dc short-circuit value.
A neutralizing agent, rubber gloves and containment bag are part of a _________.
Question 86 of 100
86. Question
A field-expedient neutralizing agent is ______.
Question 87 of 100
87. Question
What type of hazard is created when two workers remove damaged Li-ion modules from a system?
Question 88 of 100
88. Question
NFPA 70E, Article 320 states that it is ok to wear metal jewelry such as a watch or ring as long as it is covered by insulated rubber or leather gloves.
Question 89 of 100
89. Question
NFPA 70E 110.6(A)(1) states that employees do not have to be trained on an appropriate test instrument to verify the absence of voltage if a battery energy storage system is locked out and tagged out.
Question 90 of 100
90. Question
Article 130.5 states that it is acceptable to use the results of an incident energy analysis to specify the Arc Flash PPE Category from Table 130.7(C)(16).
Question 91 of 100
91. Question
NFPA 70E 110.6(A)(1) Qualified Person states that in addition to Article 110 general requirements for ESRWP workers shall also be familiar with:
Question 92 of 100
92. Question
Which of the following is not determined by a shock risk assessment performed for an energized electrical work permit?
Question 93 of 100
93. Question
According to NFPA 70E Section 110.4 Energized Work, additional hazards or increased risks include:
Question 94 of 100
94. Question
Moveable or fixed conductors and circuit parts changes the _________ boundary, but not the ________ boundary.
Question 95 of 100
95. Question
The restricted approach boundary (RAB) for dc exposure at 480 volts is:
Question 96 of 100
96. Question
NEC 480.7(C) states that battery circuits, where exceeding ________ nominal between conductors and ground, shall have provisions to disconnect the series-strings into segments.
Question 97 of 100
97. Question
Non-insulated (standard) tools can be used on segmented battery arrays.
Question 98 of 100
98. Question
According to Article 110.4(C) work on equipment operating at less than 50-volts does not need to be de-energized if it is determined there is no additional increased exposure to electrical burns or explosion due to electric arcs.
Question 99 of 100
99. Question
If a dc feeder between a battery array and disconnect needs to be removed, what end should be removed first?
Question 100 of 100
100. Question
What typically has a greater fault current?